The new Fluke 983 Particle Counter is the preferred choice for HVAC and IAQ professionals. From filter testing to IAQ investigations, the Fluke 983 is the portable solution for determining airborne particle concentrations. Use the Fluke 983 to immediately respond to occupant complaints, or as part of a comprehensive preventive maintenance program.
With the Fluke 983, you can:
Measure filter efficiency
Monitor industrial cleanrooms
Pre-screen indoor air quality and confidently work with IAQ specialists
Locate particle sources for remediation
Report the effectiveness of repairs to customers
Drive additional business by demonstrating the need for maintenance and repair
With expanded data logging and six-channel particle size display, the Fluke 983 allows users to run more tests quickly, with less time spent cycling through screens to obtain the data. The Fluke 983 is lightweight and easy to use in any position, with a comfortable hand strap and rugged rubber holster.
| Specifications |
| Channels |
|
0.3, 0.5, 1.0, 2.0, 5.0, 10.0 µm |
|
| Flow Rate |
|
0.1 cfm (2.83 L/min) controlled by internal pump |
|
| Count Modes |
|
Concentration, totalize, audio |
|
| Counting Efficiency |
|
50% @0.3 µm; 100% for particles > 0.45 µm (per JIS B9921:1997) |
|
| Zero Count |
|
1 count/5 minute (JIS B9921:1997) |
|
| Coincidence Loss |
|
5% at 2,000,000 particles per ft3 |
|
| Relative Humidity |
|
± 7%, 20% to 90% non-condensing |
|
| Temperature |
|
± 3 ˚C, 10 ˚C to 40 ˚C (50 ˚F to 104 ˚F) |
|
| Data Storage |
|
5000 sample records (rotating buffer) of date, time, counts, relative humidity, temperature, sample volumes, alarms, label |
|
| Alarms |
|
Counts, low battery, sensor fail |
|
| Delay Time |
|
| Sample Inlet |
|
| Interface |
|
RS-232 and RS-485 via RJ-45 |
|
| Environmental Specifications |
| Operating: |
|
10 ˚C to 40 ˚C (50 ˚F to 104 ˚F), 20% to 90% relative humidity, non-condensing |
|
| Storage: |
|
-10 ˚C to 50 ˚C (14 ˚F to 122 ˚F), up to 90% relative humidity, non-condensing |
|
| Mechanical & General Specifications |
| Size |
|
11.43 cm x 20.96 cm x 5.72 cm (4.5 in x 8.25 in x 2.25 in) |
|
Dimensions (W x L x D) |
|
| Weight |
|
| Power |
|
AC adapter, 12 V DC at 2.5A, 90 to 250 V AC, 50 to 60 Hz |
|
| Rechargeable Battery |
|
NiMH, 4.8 V at 4.5 Ah; replaceable |
|
| Battery Life |
|
| Recharge Time |
|
| Calibration |
|
PSL particles in air (NIST traceable) |
|
.
|