The TSI Model 8375 Accubalance Capture Hood is a multipurpose electronic air balancing instrument for reading air volume flow at diffusers, and grilles. It is ideally suited for commissioning agents, facilities managers, health and safety specialists, test engineers, and test and balance professionals. This ultra light weight, ergonomically designed kit saves time and money while helping to create a healthy and energy efficient environment. Applications include thermal comfort studies, HVAC testing, adjusting and balancing, as well as air volume measurements.

 
FEATURES AND BENEFITS:
  • Ergonomic design and ultra light weight for easy one person operation
  • Detachable digital manometer for use in other applications with Pitot, airflow,temperature, velocity matrix, or relative humidity probes.
  • Back pressure compensate  Multiple hood sizes available
  • Bio-Safety hood kit available
 
INCLUDED ITEMS:
  • Instrument
  • 2'x2' hood with frame and support poles
  • Wheeled carrying case
  • 18-inch pitot probe
  • Static pressure probes
  • 16' Neoprene tubing
  • Logdata downloading software with cable
  • Neck strap
  • (4) AA rechargeable NiMH batteries and 2 battery holders
  • Internal battery charger
  • NIST traceable calibration certificate
  • User manual
  • Multi-country AC power adaptor

 

Specifications
Volume 
Range 25 to 2,500 ft 3/min (42 to 4250 m3/h) capture hood
Accuracy 3% of reading 7 ft 3/min
(12 m3/h) at flows >50 ft 3/min (>85 m3/h)
Units ft 3/min, m3/h, m3/min, l/s
Resolution 1 ft 3/min (1 m3/h)
Velocity
Range (Pitot Probes) 25 to 8,000 ft/min (0.125 to 40 m/s)
Range (Airflow Probe) 25 to 5,000 ft/min (0.125 to 25 m/s)
Velocity Matrix 25 to 2,500 ft/min (0.125 to 12.5 m/s)
Accuracy 3% of reading 7 ft/min (0.04 m/s) at
velocities >50 ft/min (0.25 m/s) 3% of reading 7 ft/min (0.04 m/s) at
velocities >50 ft/min (0.25 m/s)
Units ft/min, m/s
Resolution 1 ft/min (0.01 m/s)
Pressure
Differential Pressure 15 in. H2O (3735 Pa ); 150 in. H2O
(37.5 kPa) maximum safe operating pressure  
Absolute Pressure 15 to 40 in. Hg (356 to 1016 mm Hg)
Accuracy 2% of reading 0.001 in. H2O (0.25 Pa )
static and differential; 2% of reading absolute
Units in. H2O, in. Hg, Pa, hPa, kPa, mm Hg, cm Hg,
mm H2O, cm H2O
Resolution 0.00001 in. H2O (0.001 Pa) static and
differential; 0.01 in. Hg (1 mm Hg) absolute
RH  
Range 0 to 95% RH temperature/RH probe
Accuracy 3% RH
Resolution 0.1% RH
Temperature
Sensor in Base 40 to 140F (4.4 to 60C)
Temperature Probe -40 to 250F (-40 to 121C)
Temperature/RH Probe 14 to 140F (-10 to 60C)
Accuracy 0.5 F (0.3C) from 32 to 160F(0 to 71C)
Units F, C
Resolution  0.1F (0.1C)
 