null

Retrotec Acin FlowFinder Mk2+ Powered Flow Hood

SKU:
FF100+US
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS - Powered Flow Hood
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS - Powered Flow Hood includes
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS no hood
  • Retrotec Acin FlowFinder Mk2+ Powered Flow Hood
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS no hood on side
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS screen
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS - Powered Flow Hood in case
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS - Powered Flow Hood in case above
  • Retrotec FF100+US Acin FlowFinder MK2 PLUS - Powered Flow Hood empty case above
Price: $3,550.00

Description

Retrotec Acin FlowFinder Mk2+ Powered Flow Hood

The improved mk2 PLUS has faster speeds, smarter control, WiFi connectivity and more

The newly enhanced FlowFinder-mk2+ is packed with exciting new features and benefits, including hardware and control software enhancements, significantly boosting your device's performance and functionality.

The FlowFinder-mk2+ represents a cutting-edge powered flow hood that excels in diverse scenarios. When confronted with low duct pressure, it exhibits exceptional precision in zeroing the pressure across the measurement plane, ensuring minimal disruption to system characteristics. While many powered flow hoods perform adequately in return/exhaust flows, the FlowFinder-mk2+ stands out by achieving remarkable zeroing down to 1/100 Pa, surpassing the typical range of zero to approximately 2/10 Pa observed in most counterparts. Consequently, the FlowFinder-mk2+ proves particularly advantageous in situations involving low pressures or alternative air pathways.

With the ability to measure a range of 6 to 500 CFM with no compensation (firmware v3.14 or higher), the FlowFinder-mk2+ combines exceptional functionality with its compact and lightweight design, making it suitable for measuring kitchen exhaust and HRV flows in confined spaces. However, its true "Killer" application emerges when deployed in conjunction with a Blower Door during sales calls, allowing for the visual and quantitative assessment of duct leakage to the outdoors. By pressurizing the house to 25 Pa using the Blower Door, any smoke movement detected at the registers can be precisely measured by the FlowFinder-mk2+, empowering operators to identify the most cost-effective improvements that can be undertaken for a home.

Key Features and Benefits

  • Faster Operation: The upgraded FlowFinder-mk2+ will operate at an impressive 50 Hz, a substantial improvement from the previous 2 Hz. This increase in speed enables quicker data acquisition and more responsive control actions
  • Enhanced Stability: The hardware (display PCB) and control software improvements ensure excellent stability, reducing the likelihood of errors or disruptions during measurements and control processes. You can rely on the upgraded FlowFinder-mk2+ for accurate and reliable results
  • Upgradable via WiFi: The new brain equipped with WiFi connectivity allows for seamless upgrades and updates without needing physical connections or manual intervention. Enjoy the convenience of wireless upgrades and take advantage of future enhancements effortlessly
  • Improved Battery Efficiency: With faster and more stable measurements at higher flows, the upgraded FlowFinder-mk2+ reduces the time required for data collection. Measurements at higher flows, now up to 500 CFM from the previous 300 CFM, will take less than 10 seconds. This increased efficiency translates into battery savings, providing more extended operation between charges. Replacement battery pack available
  • Two Bootloaders: Implementing two bootloaders ensures a streamlined and secure upgrade process for your FlowFinder-mk2+. This feature minimizes the risk of issues during firmware upgrades, allowing for safer and more straightforward updates

The FlowFinder-mk2 PLUS offers you the following improvements over the standard mk2

  • The full volume flow range from 10 to 850 m3/h is now supported with zero pressure compensation
  • Increased measurement speed from 2 to 50 measurements per second
  • The duration of a validation measurement can be reduced from 14 to 10 seconds
  • The adjustment mode (now called "continuous") is faster, more stable, and now also provides information about measurement stability
  • Lower power consumption at high flow rates, the motor only needs to support for a few seconds allowing longer operation per battery charge and sufficient power for higher flow rates
  • Now equipped with WiFi, allowing users to update the firmware themselves via PC
  • Startup time is now significantly faster
  • Future software updates will be provided free of charge
  • Future app support

Specs

FlowFinder Mk2+ Flow Hood Specifications
Volume flow
(with zero pressure compensation)
Range: 6 – 500 CFM (10 – 850 m3/h)
Accuracy: ± 3% (at 68 °F / 20 °C)
Temperature Range: –4 °F to 176 °F (–20 °C to 80 °C)
Accuracy: ± 0.3 K (at 73.4 °F / 23 °C)
Air humidity Range: 0 – 99.9 %
Accuracy: ± 3 % (at 73.4 °F / 23 °C)
Air pressure Range: 8.85 – 32.48 inHg (300 – 1100 hPa)
Accuracy: ± 1 hPa
Battery NiMh battery; 14.4 V, 2200 mAh
Battery Life 8 hours at volume flows up to 200 m3/h
Display Touchscreen
Dimensions (FlowFinder) 10.2 × 10.2 × 13.8 in (260 × 260 × 350 mm)
Dimensions (Case) 12.4 × 12.4 × 14.6 in (315 × 315 × 370 mm)
Storage Internal
Operating and storage temperature 41 °F to 104 °F (5 – 40 °C)

Includes

  • (1) FlowFinder Mk2+ Flow Hood
  • (1) Clear Flow Hood (16x16)
  • (1) Retrotec FlowFinder Soft Case
  • (1) Battery Pack
  • (1) Battery Charger
  • (1) Calibration Certificate