Macurco CM-6 can be used stand-alone controller and detector. It can also be used as a analog transducer with the DV_120 and other systems.
Places the CM-6 can be used in are parking garages, maintenance facilities and other commercial applications.
The unit typically covers about 5,000 sq.ft. (465 square meters) in a parking garage or similar application and 900 sq.ft. (84 square meters) in a residential or office type application. The coverage depends on air movement within the room or facility. Do not mount the CM-6 in a corner. The detector may be installed on either a ceiling or a wall. If installed on a peaked, gabled, or sloped ceiling, it should be located about 3 feet (1 meter) from the highest point. Normally, the unit is mounted about 5 feet (1.5m) above the floor (normal breathing zone), in a central area where air movement is generally good. Additional detectors may be needed near any areas where people work or where the air is stagnant.