null

Dwyer 2002 Magnehelic® Differential Pressure Air Filter Gauge, 0 to 2" WC

SKU:
2002
MPN:
2002
Minimum Purchase:
1 unit
  • Dwyer 2002 Magnehelic® Differential Pressure Air Filter Gauge main front view
Price: $88.10

Description

Dwyer 2002 Magnehelic® Differential Pressure Air Filter Gauge, 0 to 2" WC

Control the Critical with the Series 2000 Magnehelic®

Designed in the USA and time-tested in critical locations around the world, the authentic Magnehelic® differential pressure gauge is used in applications including filter status monitoring, duct or building pressure, and clean room pressure indication.

The Magnehelic® gauge consists of two pressure-tight compartments separated by a flexible diaphragm. The interior of the case serves as the high-pressure side, while a sealed chamber behind the diaphragm serves as the low-pressure side. Differences in pressure cause the diaphragm to move, and its motion is transmitted to the pointer. The gauge requires no maintenance, with only occasional zero adjustment performed by opening the plastic vent valves and turning the pointer adjustment.

Key Features & Benefits

  • Trusted, Patented Design
    • Industry leader for pressure monitoring
    • Precision calibrated for exacting measurements
    • Resists shock and vibration, and protected for over-pressures
  • Long Service Life
    • Designed in the USA using high quality components
    • Clear acrylic face resists both fading and color changes over time
    • 5 year manufacturer warranty
  • Installation Flexibility
    • No power is required to analog gauge
    • Durable and rugged IP67 weatherproof housing with diecast aluminum case

Applications for Use

  • Filter status monitoring in air handler units

    Dwyer's Magnehelic® gauge allows for a quick visual status check of the pressure across filters. A significant pressure difference across the filter can be a sign that there is decreased air flow. Monitoring the differential pressure will help to indicate when filter replacement is needed, or if damper blockages and malfunctions are present.

  • Filter monitoring in dust collectors

    Over time, dust accumulates on the filter of dust collectors, so periodic cleaning is important to maintain continuous operation. When the pressure drop indicates that cleaning is necessary, a timer controller is manually activated to initiate a cleaning cycle which involves solenoid valves releasing pulses of air.

  • Pressure monitoring of scrubber & fume exhaust systems

    Dwyer's Magnehelic® gauge monitors pressure within fab/subfab scrubbers and fume exhaust systems. Visual status informs the system owner of real-time negative and positive pressures. It also assists with balancing system laterals and mains throughout the fab/subfab facilities.

  • Room pressure monitoring for hospital isolation rooms

    The Magnehelic® gauge is used in hospitals all over the world. When an isolation room is kept at a negative pressure in relation to the anteroom, air from the anteroom will be pulled into the isolation room. This negative pressure relation will prevent pathogens from escaping as no air can leave the isolation room.


Specs

Dwyer 2002 Magnehelic Specs
Measurement Pressure Type Differential
Measurement Pressure, Max 2 inH2O
Measurement Pressure, Min 0 inH2O
Accuracy ± 2 %
Accuracy Detail ± 2 % (-HA model ± 1) of FS (± 3 % (-HA ± 1.5 %) on -0, -100PA, -125PA, -10MM
± 4 % (-HA ± 2 %) on -00, -60PA, -6MM ranges), throughout range at 70°F (21.1°C)
Pressure Limits -20 inHg to 15 psig
Process Connection Note 1/8″ female NPT duplicate high and low pressure taps - one pair side and one pair back
Process Connection Size 1/8 in
Process Connection Type NPT Female
Dial Dia 4 in
Dual false
Enclosure Ratings IP67
Material Construction Option Standard
Materials Aluminum, Acrylic
Compliance RoHS 2
Compliance Note Meets the technical requirements of EU Directive 2011/65/EU (RoHS II). Note: -SP models not RoHS approved
Media Compatibility Air, Argon, Carbon dioxide, Helium, Nitrogen, Non-Corrosive Dry Gases
Mounting Orientation Vertical Diaphragm
Operating Temperature, Max 140 °F
Operating Temperature, Min 20 °F
Safety Features Relief plug opens at approximately 25 psig (1.72 bar), standard gauges only
Weight 18 oz (510 g)

Includes

  • (1) Dwyer 2002 Magnehelic® Differential Pressure Gauge 0 to 2" WC